Stabilizer Model: PSS3B
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Tw1 < Mult*TimeStep then Tw1 = Mult*TimeStep
- If 0 < Tw2 < Mult*TimeStep then Tw2 = Mult*TimeStep
- If 0.0 < Tw3 < 0.5*Mult*TimeStep then Tw3 = 0, ElseIf 0.5*Mult*TimeStep < Tw3 < Mult*TimeStep then Tw3 = Mult*TimeStep
- If 0.0 < T1 < 0.5*Mult*TimeStep then T1 = 0, ElseIf 0.5*Mult*TimeStep < T1 < Mult*TimeStep then T1 = Mult*TimeStep
- If 0.0 < T2 < 0.5*Mult*TimeStep then T2 = 0, ElseIf 0.5*Mult*TimeStep < T2 < Mult*TimeStep then T2 = Mult*TimeStep
- If Vstmax < Vstmin then swap the values. If Vstmax < 0 then Vstmax change sign to positive. If Vstmin > 0 then change sign to negative.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Ics1 | First stabilizer input code |
| Ics2 | Second stabilizer input code |
| K1 | Signal gain |
| T1 | Transducter time constant, sec |
| Tw1 | Washout time constant, sec |
| K2 | Signal gain |
| T2 | Transducter time constant, sec |
| Tw2 | Washout time constant, sec |
| Tw3 | Washout time constant, sec |
| A1 | Notch filter parameter |
| A2 | Notch filter parameter |
| A3 | Notch filter parameter |
| A4 | Notch filter parameter |
| A5 | Notch filter parameter |
| A6 | Notch filter parameter |
| A7 | Notch filter parameter |
| A8 | Notch filter parameter |
| Vstmax | Output limit, maximum |
| Vstmin | Output limit, minimum |